2111 interbus fieldbus module, Show/hide bookmarks – Lenze EMF2111IB User Manual
Page 35
Data transfer
Process data signals of Lenze controllers
5
2111 INTERBUS fieldbus module
5.6
5.6.2
L
5.6-13
EDSIBS-1.0-06/2003
Control word AIF-CTRL for 8200 vector (Lenze code C0135, index 5F78
hex
)
AIF-CTRL.Bxx
Default setting:
C0001=3 if C0007 ≤ 51
Default setting:
C0001=3 if C0007 > 51
Adjustable in L-C0410/..
00,
00 = C0046 active
01 = NSET1-JOG1 (C0037) active
1
00,
01
01
NSET1 JOG1 (C0037) active
10 = NSET1-JOG2 (C0038) active
11 = NSET1-JOG3 (C0039) active
Freely configurable by user
1
2
02
DCTRL1-CW/CCW
0 = not active
1 = active
3
03
AIF-CTRL-QSP
0 = not active
1 = active
AIF-CTRL-QSP
0 = not active
1 = active
4
04
NSET1-RFG1-STOP
0 = not active
1 = active
5
05
NSET1-RFG1-0
0 = not active
1 = active
6
06
MPOT1-UP
0 = not active
1 = active
Freely configurable by user
7
07
MPOT1-DOWN
0 = not active
1 = active
8
08
Freely configurable by user
9
09
AIF-CTRL-CINH
0 = not active
1 = active
AIF-CTRL-CINH
0 = not active
1 = active
10
10
AIF-CTRL-TRIP-SET
0 = not active
1 = active
AIF-CTRL-TRIP-SET
0 = not active
1 = active
11
11
AIF-CTRL-TRIP-RESET
0 -> 1 = Edge from 0 to 1 AIF-CTRL-TRIP-RESET
0 -> 1 = Edge from 0 to 1 12
12
DCTRL1-PAR2/4
0 = not active
1 = active
13
13
DCTRL1-PAR3/4
0 = not active
1 = active
Freely configurable by user
14
14
MCTRL1-DCB
0 = not active
1 = active
15
15
Freely configurable by user
Freely configurable by user
16
AIF
AIF-IN
AIF-CTRL
AIF-IN.W2
AIF-IN.W1
.B15
.B12
.B0
.B1
.B2
.B3
.B4
...
...
...
...
...
...
...
...
...
...
...
...
.B8
.B9
.B10
.B11
DCTRL
QSP
CINH
TRIP-SET
TRIP-RESET
DCTRL
16 bits
16 bits
16 bits
2141LON011_en
Fig. 5.6-4
Function block AIF-IN in 8200 vector (freely programmable assignment)