Data transfer
DRIVECOM profile parameters
5
2111 INTERBUS fieldbus module
5.6
5.6.7
L
5.6-39
EDSIBS-1.0-06/2003
Bit
Name
Meaning
0
Ready to switch
on
Controller status information
0 = Status lower than ”READY TO SWITCH ON“
1 = Status at least ”READY TO SWITCH ON“
1
Switched on
Controller status information
0 = Status lower than ”SWITCHED ON“
1 = Status at least ”SWITCHED ON“
2
Operation
enabled
Controller status information
0 = Status lower than ”OPERATION ENABLED“
1 = Status ”OPERATION ENABLED“
3
Fault
Controller status information
0 = No fault (TRIP))
1 = Fault (TRIP) occured
4
Voltage inhibited Information about the command ”voltage inhibit“ (see chapter 5.6.7.4 ”control word“)
0 = Command active
1 = Command not active
5
Quick stop
Information about the command ”quick stop“ (see chapter 5.6.7.4 ”control word“)
0 = Command active
1 = Command not active
6
Switch-on
inhibit
Controller status information
0 = Statu not ”SWITCH-ON INHIBIT“
1 = Status ”SWITCH-ON INHIBIT“
7
Warning
Collective warning
0 = No warning
1 = Warning (overtemperature)
8
Meldung
Collective message. Automatic setting and resetting of pulse inhibit in the controller status
”OPERATION ENABLED”. Reasons for this can be undervoltage or overvoltage as well as
overcurrent (clamp).
0 = No message
1 = Message (IMP)
9
Remote
82XX, 821X, 822X,
8200 vector:
93XX:
Bus access, depends on Lenze parameter ”operating mode”
(L-C0001):
0 = L-C0001 <> 3 or L-C1911 = 0
1 = L-C0001 = 3 and L-C1911 = 1
0 = L-C1911 = 0
1 = L-C1911 = 1
10
FREE
DRIVECOM:
Setpoint
reached
Status of speed/frequency deviation
0 = RFG
on
<> RFG
off
1 = RFG
on
= RFG
off
11
Limit value
Status of the DRIVECOM speed limitation
0 = Limitation not addressed
1 = Limitation addressed
12
FREE
DRIVECOM:
Reserve
820X, 821X, 822X:
8200 vector, 93XX:
Not assigned
Free. Mapping to bit L-C0150.B14
13
FREE
DRIVECOM:
Reserve
82XX:
8200 vector:
93XX:
Not assigned
Free. Mapping to bit L-C0150.B15
Free. Mapping to bit L-C0150.B3
14
Manufacturer
820X, 821X, 822X:
8200 vector, 93XX:
I
max
(current limit reached)
0 = Current limit not reached
1 = Current limit exceeded
Free. Mapping to bit L-C0150.B2
15
Manufacturer
820X, 821X, 822X:
8200 vector, 93XX:
Q
min
(f
d
≤ f
dQmin
)
0 = Q
min
not active
1 = Q
min
active
Free. Mapping to bit L-C0150.B5
Structure of the DRIVECOM
status word