7 Configuration

60

7.6 Interfaces „INTERFCE“

The interface parameters for the RS422/485 or
PROFIBUS-DP interface have to be configured in
order to communicate with PCs, bus systems and
peripheral devices.

Configuration

Analog inputs
Limit
comparators
Outputs
Binary
functions
Display /
Operation
Interfaces

RS422485 (Modbus)

Parameter

Value/

Selection

Description

Protocol

P R O T O C O L

0
1

Modbus
Modbus integer

Baud rate

BAUD RATE

0
1
2

9600 bps
19200 bps
38400 bps

Data
format

DFORMAT

0
1
2
3

8 data bits, 1 stop bit, no parity
8 data bits, 1 stop bit, odd parity
8 data bits, 1 stop bit, even parity
8 data bits, 2 stop bits, no parity

Device address

ADDRESS

0…1

255

Address in data network

Min. response
time

(Setup)

0…500

Time period in milli-seconds that elapses
between the request of a device in the data
network and the response of the display
instrument.

Adjustment only possible in the setup
program:
-> Interfaces -> RS422/RS485

Factory settings are shown bold.