4 Electrical connection

4.4 Termination resistor for the RS422/485 interface

Setting
resistors

To ensure fault-free operation of several instruments
in a line structure, their internal termination resistors
must be activated at the start and end

.

h Pull plug-in module out towards the front by

pressing on the knurled areas

h Using a suitable aid (e.g. ballpoint pen), press all the

white switches into the same direction

h Re-insert the module into the housing

Check

h Press the

P

+

i

keys

When checking the software version and the
termination resistors activated, an additional decimal
point appears behind the version number (top
display).

Example of version number 01.01:
active:

01.01.

inactive:

01.01

Bus
termination
active

h Push all 5 switches down

No
bus
termination
(ex-factory)

h Push all 5 switches up