beautypg.com

7 configuration – JUMO 701550 di 308 - Digital Indicator Operating Manual User Manual

Page 47

background image

47

7 Configuration

LIMITC 1 (limit comparator 1)
LIMITC 2 (limit comparator 2)
LIMITC 3 (limit comparator 3)
LIMITC 4 (limit comparator 4)

Parameter

Value/

Selection

Description

Function

FUNCTION

0
1
2
3
4
5
6
7
8

no function
lk1
lk2
lk3
lk4
lk5
lk6
lk7
lk8

Limit value

LIMVALUE

-19999…
0
99999

Limit value to be monitored
(see limit comparator functions lk1...lk8:
limit value AL)

Hysteresis

HYSTERES 0…1

99999

Switching differential in respect to the limit
value
(see limit comparator functions lk1...lk8:
hysteresis HySt)

Fixed limit
comparator
setpoint value

FIXLCVAL

-19999…
0
99999

A fixed setpoint value can be set for the
limit comparator (lk1...lk6).

The limit comparator setpoint value
LCSETVAL must be deactivated for the
fixed setpoint value to be active.

Action/
Range response

ACT-RESP

0
1
2
3

absolute/off
relative/off
absolute/on
relative/on

Defines the switching action of the limit
comparator and the switch status for an
overrange or underrange (signal at „Out of
Range“).

See description on page 49.

Switch-on delay ON DELAY

0…9999

Delays the switch-on edge by a definable
time period (time in seconds).

Switch-off delay OFFDELAY

0…9999

Delays the switch-off edge by a definable
time period (time in seconds).

Factory settings are shown bold.