7 Configuration

OUTANALG (analog outputs) Output 5

Output 6
Output 7

Parameter

Value/

Selection

Description

Function

F U N C T I O N (analog

selector)
deactivated

Function of the output

v „Analog selector“, page 34

Type of signal

S I G N A L

0
1
2
3

0...10V
2...10V
0...20mA
4...20mA

Physical output signal

Range error

R A N G E R R 0…101

Output signal (in % of the value range) for
an overrange or underrange.
101=last output signal

Scale low point

S C A L - L O W -19999…

0
99999

A value range of the output variable is
assigned to a physical output signal. The
ex-factory setting corresponds to an output
variable with a value range of 0...100.

Example:
Via an analog output (0 … 20mA), a
temperature ranging between 150 … 500°C
is to be output.
i.e.: 150 … 500°C

־ 0 … 20mA

Scale low point: 150 / Scale high point: 500

Scale high point SCAL-HI

-19999…
100
99999

Offset

(Setup)

-19999…
0
99999

The offset is used to correct the output
signal by a certain amount upwards or
downwards.

Examples:
Original

Output

value

Offset

value

294.7

+0.3

295.0

295.3

-

0.3

295.0

To enter digits after the decimal point, the
value of system point must be set
accordingly (see page 57).

Adjustment only possible in the setup
program:
-> Outputs -> Analog outputs

Factory settings are shown bold.