Program Specifications
Programs:
Eight, each with free-form segments
Length of Programs:
Adjustable in the range 1 to 16 segments; programs
cascadable - maximum length 121 segments.
Segment Types:
Ramp, Dwell, Join, Repeat, or End.
Program Cycling:
Range 1 to 9999, infinite.
Delayed Start:
May be set in the range 0 to 99:59 (hours:minutes).
One setting applies to all programs.
Control:
Run, Hold, Abort, Time Base x60 (local or remote);
Select Program (local or remote); Jump to next Segment.
Start From:
Either current process variable value or controller setpoint value.
Go To:
Base Mode or Off Mode
End On:
Final Value or controller setpoint.
Deviation/Hold:
Off, below setpoint only, above setpoint only or above and below
setpoint. On ramps only, on dwells only, or on both ramps and
dwells. Auto/Hold band may be set from 0 to input span.
Time Base:
Either hours:minutes or minutes:secs (x60) preprogrammable or
may be set during Program Run.
Segment Time:
May be set in the range 0 to 99:59 (hours:minutes or
minutes:seconds).
Ramp Rate:
0 to 9999 least significant digits per hour or minute.
End of Program Output
Type:
Relay
Contact Type:
SPDT
Rating:
5A resistive @ 120/240V AC
Lifetime:
>100,000 operations @ rated voltage/current
Isolation:
Inherent
Event Outputs - Option
Type:
Relay (4)
Contact Type:
SPST
Rating:
5A resistive @ 120/240V AC
Lifetime:
>100,000 operations @ rated voltage/current.
Isolation:
Inherent
Programmability:
Each event is programmable to either OFF or ON for each segment.