Control Specifications


Control Types:

PID, PID/ON-OFF2, ON-OFF

Automatic Tuning Types: Pre-Tune and Auto-Tune
Proportional Bands:

0 (OFF) 0.5% - 999.9% of input span @ 0. 1 % increments

Auto Reset:

1 s-99min 59sec/repeat and OFF

Rate:

0 (OFF) - 99min 59sec

Manual Reset (Bias):

Adjustable in the range 0-100% of output power (single output) or -
100% to +100% of output power (dual output)

Deadband/Overlap:

-20% to +20% of proportional band 1 + proportional band 2

ON/OFF Hysteresis:

0. 1 % to 10.0% of input span

Auto/Manual Control:

User-selectable with "bumpless" transfer into and out of Manual
control.

Cycle Times:

Selectable from 0.5sec to 512sec in binary steps

Setpoint Range:

Limited by Setpoint Maximum and Setpoint Minimum.

Setpoint Maximum:

Limited by Setpoint and Range Maximum.

Setpoint Minimum:

Limited by Range Minimum and Setpoint.



Alarms
Maximum Number:

Two "soft" alarms plus Loop Alarm

Maximum # Outputs:

Up to 2 outputs can be used for alarm purposes

Combination Alarms:

Logical OR or AND of alarms to an individual
hardware output is available.

Hysteresis:

1 LSD to 1 0% of span.

Loop Alarm:

Detects faults in the control feedback loop by continuously
monitoring process variable response to the control output(s).