beautypg.com

Despatch MIC1462 Controller Manual User Manual

Page 74

background image

70

10.4 Controller Parameters


The Controller parameters appear in the following sequence:

STEP

DESCRIPTION

MESSAGE
DISPLAY

FUNCTION

AVAILABLE SETTING

11

Scale Range
Decimal Point

9

DecPos

For linear inputs, defines
the decimal point position

0 XXXX
1 XXX.X (default)
2 XX.XX
3 X.XXX

12

Scale Range
Maximum

9

EngU UP

For linear inputs, defines
the scaled input value when
the process variable input is
at its maximum value.

-1999 to 9999 (decimal
point as defined by Scale
Range Decimal Point
parameter) Default = 0.0

13

Scale Range
Minimum

9

EngU LO

For linear inputs, defines
the scaled input value when
the process variable input is
at its minimum value.

-1999 to 9999 (decimal
point as defined by Scale
Range Decimal Point
parameter) Default = 0.0

14

Setpoint High Limit

8

SP High

The maximum limit for
setpoint adjustment.
Should be set to a value
which prevents setpoint
values causing damage to
the process.

Current setpoint value to
input Range Mx.
Default = Input
Range Max.

15

Setpoint Low Limit

8

SP Low

The minimum limit for
setpoint adjustment.
Should be set to a value
which prevents setpoint
values causing damage to
the process.

Input Range Min. to
current setpoint value.
Default = Input Range
Minimum.

16

Input Filter Time
Constant

Filter

Defines time constant for
input filter (removes
extraneous impulse from
the process variable input).

0.0 seconds (filter OFF) to
100.0 seconds in 0.5
increments. Default = 2.0
seconds.

17

Output Power Limit

Out PL

Determines maximum
output setting instrument
will provide.

0 to 100 (%)

18

Engineering Units

9

Units

Sets units to be displayed in
base mode.

Unit
CEnt
FAHr

19

End of program
output relay

EOPrelay

Sets action of relay

End = relay active at end
of profile
run = relay active during
profile
Default = End