EXIT FROM CALIBRATION MODE

To exit from Calibration Mode, cycle power to the instrument.

NOTE: An automatic exit is made from Calibration Mode if there is no key activity for
two minutes.


CALIBRATION CHECK

1. Set the Controller to the required configuration (using link jumpers and front panel

entry) as described in the appropriate Site Manual.


2. Power-up the Controller and leave it powered-up for at least five minutes (for RTD

and DC linear inputs) or at least 30 minutes (for thermocouple inputs).


3. After the appropriate delay for stabilization has elapsed, check the calibration by

connecting the appropriate input source and checking a number of cardinal points.