SECTION 8: ALARM MODE


The Alarm Mode parameters control the type of alarms used and their settings.

To enter the Alarm Setting Mode from Base Mode:

1. Press the MODE key until Alarm appears in the message display

2. Press the SCROLL key to enter the Alarm Setting Mode.

To return to Base Mode:

1. Press the MODE key until Basemode appears in the message display.

2. Press the SCROLL key to return to Base Mode.

Press the SCROLL key to step through the parameters. Press the UP and DOWN keys
to change the parameter setting.
Table 8-1

Alarm Mode Parameters

STEP

DESCRIPTION

MESSAGE
DISPLAY

FUNCTION

AVAILABLE SETTING

1

Alarm 1 Type

Alarm 1

Specifies Alarm 1 Operation

P_hi - Process High
P_Lo - Process Low
dE - Deviation
bAnd - Band
nonE - None

2

Alarm 2 Type

Alarm 2

Specifies Alarm 2 Operation

P_hi - Process High
P_Lo - Process Low
dE - Deviation
bAnd - Band
nonE - None

3

Alarm Inhibit

Inhibit

Specifies which alarms are inhibited

nonE - No inhibit
ALA1 - Alarm 1
ALA2 - Alarm 2
both - Both Alarms

4a

Process High
Alarm 1 value

HiAlarm 1

If Alarm 1 is a Process High alarm,
the value of process variable at or
above which Alarm 1 will be active

Input Range Max. to
Input Range Min.
Default = Input Range
Max.

4b

Process Low
Alarm 1 value

LoAlarm 1

If Alarm 1 is Process Low Alarm, the
value of process variable at or below
which Alarm 1 will be active

Input Range
Max. to Input
Range Min.
Default =
Input Range Min.

4c

Band Alarm 1
value

BaAlarm 1

If Alarm 1 is a Band Alarm, the band
of process variable values (centered
on the setpoint) outside which the
process variable will cause this alarm
to be active.

± (input span) from
setpoint. Default =
five input units.