Rear Panel

MX410/MX412 System Manual

4-4

PRELIMINARY

61189500L1-1B

Alarm Contacts/AUX Inputs

The alarm contacts and auxiliary (AUX) inputs are shown in

Figure 4-4

.

Figure 4-4. Alarm Contacts and AUX Inputs

The alarm interfaces connect to the nine Form C type relays on the MX410/MX412 labeled

CRIT

,

MAJOR

, and

MINOR

. Both NC (Normally Closed) and NO (Normally Open) contacts are

provided. Connect the

CRIT

(Critical),

MAJOR

, and

MINOR

alarm leads from the fuse and alarm

panel to the

C

(Common) and

NO

or

NC

wire-wrap terminals on the MX410/MX412 rear panel

as required.
Auxiliary alarms 1-4 connect to the MX410/MX412

AUX INPUTS

labeled

1

-

9

. These pins detect

open and closed relay contacts and are not polarity sensitive.

Table 4-1

shows the pin assign-

ments for the

AUX INPUTS

.

The alarm severity level can be changed in the Environmental Alarms menu.
After the alarm contact and AUX input connections have been made, install the protective
cover over the wire-wrap headers.

Table 4-1. AUX Inputs 1-9 Pin List

AUX INPUT

Function

Default Severity Level

1, 2

Alarm 1

Critical

3, 4

Alarm 2

Major

5, 6

Alarm 3

Minor

7, 8

Alarm 4

Alert

9

No Connect

N/A