Alarm contacts/aux inputs, Alarm contacts/aux inputs -4, Figure 4-4. alarm contacts and aux inputs -4 – ADTRAN MX410 User Manual
Page 42: Table 4-1, Aux inputs 1-9 pin list -4
![background image](/manuals/43772/42/background.png)
Rear Panel
MX410/MX412 System Manual
4-4
PRELIMINARY
61189500L1-1B
Alarm Contacts/AUX Inputs
The alarm contacts and auxiliary (AUX) inputs are shown in
Figure 4-4. Alarm Contacts and AUX Inputs
The alarm interfaces connect to the nine Form C type relays on the MX410/MX412 labeled
CRIT
,
MAJOR
, and
MINOR
. Both NC (Normally Closed) and NO (Normally Open) contacts are
provided. Connect the
CRIT
(Critical),
MAJOR
, and
MINOR
alarm leads from the fuse and alarm
panel to the
C
(Common) and
NO
or
NC
wire-wrap terminals on the MX410/MX412 rear panel
as required.
Auxiliary alarms 1-4 connect to the MX410/MX412
AUX INPUTS
labeled
1
-
9
. These pins detect
open and closed relay contacts and are not polarity sensitive.
shows the pin assign-
ments for the
AUX INPUTS
.
The alarm severity level can be changed in the Environmental Alarms menu.
After the alarm contact and AUX input connections have been made, install the protective
cover over the wire-wrap headers.
Table 4-1. AUX Inputs 1-9 Pin List
AUX INPUT
Function
Default Severity Level
1, 2
Alarm 1
Critical
3, 4
Alarm 2
Major
5, 6
Alarm 3
Minor
7, 8
Alarm 4
Alert
9
No Connect
N/A