Section 2

Engineering Guidelines

GENERAL

This section provides engineering guidelines for network designers who are incorporating an
MX410 or MX412 system into their network.

POWER REQUIREMENTS

Table 2-1

provides the current draw at –48 VDC (operating range of –42 VDC to –60 VDC) and

±24 VDC (operating range of ±22 VDC to ±27 VDC) with redundant PSUs installed.

Table 2-2

provides data for determining the recommended fuse for the fuse and alarm panel

that services the MX410/MX412.

Table 2-1. Current Draw at –48 VDC and ±24 VDC

Part Number

Equipment

Maximum Current Draw

at –48 VDC

Maximum Current Draw

at ±24 VDC

1189500L1

MX410

0.23 amps

0.41 amps

1189512L1

MX412

0.36 amps

0.76 amps

Table 2-2. Fuse Recommendations

System Voltage

Recommended Fuse

–48 VDC

2 amps, slow-blow

±24 VDC

2 amps, slow-blow