Cable Specifications

Cable Type

Length

Specification

RS-485 *

4000 feet (1220 m) to host

Using Belden 3105A, 22AWG twisted pair, shielded 100

 cable, or

equivalent.

RS-232

15 feet (4.57 m) for RS-232
Serial modem cable
6 inch (15.24 cm) adapter

Use any RS-232 Serial modem cable specified by the modem
manufacturer.
HID Serial Adapter cable, P/N 70007

Input Circuits *

500 feet (150 m)

2-conductor, shielded, using ALPHA 1292C (22AWG) or Alpha 2421C
(18AWG), or equivalent.

Output Circuits *

500 feet (150 m)

2-conductor, using ALPHA 1172C (22AWG) or Alpha 1897C (18AWG),
or equivalent.

Wiegand

500 feet (150 m) to reader

ALPHA 1299C, 22AWG, 9-conductor, stranded, overall shield.
Fewer conductors needed if all control lines are not used.

Ethernet

328 feet (100 m)

Cat5, Cat5E, and Cat6

Power Supply
+12 VDC IN

----

Refer to your Power Supply Installation Guide.