Unit setting the pressure and temperature units, Hhcp setting the height of height correction – Vaisala PTB220 User Manual

Page 31

background image

C

HAPTER

4_____________________________________________________________

COMMISSIONING

V

AISALA

_________________________________________________________________________ 25

UNIT Setting the pressure and temperature units

UNIT x

where (* = factory setting)

x

=

hPa*
kPa
Pa
mbar
inHg
mmHg
torr
mmH

2

O

psia
C*
F

This command is used to set and inspect the pressure and internal
temperature compensation unit. The temperature unit is not confirmed
by the barometer.

Example of changing the pressure and temperature units:

>unit
P unit

: hPa

>unit C
>send
1035.19 hPa

25.9 'C

>unit torr
P unit

: torr

>unit F

(temperature unit not confirmed)

>send

776.44 torr

78.6 'F

>

HHCP Setting the height of height correction

HHCP x

The HHCP command is used to give the height for height corrected
pressure. The value is set in meters and the range, which can be used,
is -40...+40 m. Height corrected pressure is calculated according to the
following equation.

h

P

HCP

=

+

1176

.

0

(4-1)