Mmode selecting the measurement mode, On off – Vaisala PTB220 User Manual

Page 19

background image

C

HAPTER

4_____________________________________________________________

COMMISSIONING

V

AISALA

_________________________________________________________________________ 13

NOTE

Remember to give the RESET command to initialize the new sending
mode.

MMODE Selecting the measurement mode

MMODE x

where:

x =

NORMAL or FAST

The MMODE command is used to set or inspect the measurement
mode of the barometer. In the normal measurement mode, the
barometer measures the capacitance of each of the five capacitive
components of the pressure transducer (see page 6). This is the
standard operating mode of the PTB220 series digital barometers.

In the fast measurement mode, the barometer measures mainly the
capacitance of the BAROCAP

pressure sensor and results in a faster

measurement speed (approximately 10 measurements per second).
This measurement mode can be used only with the barometers having
one pressure transducer and full duplex communication.

MMODE selection is protected by switch SW4 (see

F

IGURE

4-1

). The

switch SW4 is normally in DISABLE position (OFF). Turn the switch
to ENABLE position (ON) to be able to make a new MMODE
selection.

ON

OFF

SW1

SW2

SW3

SW4

SW5

SW6

SW7

SW8

S1

F

IGURE

4-1

Switch SW4 in ENABLE position (ON)

Example of selecting the fast measurement mode:

>mmode
Meas mode

: NORMAL

>mmode fast
Meas mode

: FAST

>mtim 32