Table 44 10000-Series Enterprise 42U Rack Physical Dimensions
Configuration
Height in / mm
Width in / mm
Depth in / mm Max Wt lbs / kg
Enterprise 2C6D
78.75 / 2000.0
23.7 / 600
39.3 / 1000
918 / 416
Enterprise 2C12D
78.75 / 2000.0
23.7 / 600
39.3 / 1000
1350 / 612
Enterprise 0C6D
78.75 / 2000.0
23.7 / 600
39.3 / 1000
818 / 371
Enterprise 0C12D
78.75 / 2000.0
23.7 / 600
39.3 / 1000
1250 / 567
Table 45 10000-Series Enterprise 42U Rack Shipping Dimensions
Configurations
Height in / mm
Width in / mm
Depth in / mm
Max Wt
(packaging)
lbs / kg
Enterprise 2C6D
86.22 / 2190
32.0 / 813
48.0 / 1220
1111 / 504
Enterprise 2C12D
86.22 / 2190
32.0 / 813
48.0 / 1220
1543 / 700
Enterprise 0C6D
86.22 / 2190
32.0 / 813
48.0 / 1220
1011 / 459
Enterprise 0C12D
86.22 / 2190
32.0 / 813
48.0 / 1220
1443 / 654
Environmental specifications
To ensure optimum product operation, you must maintain the operational environmental specifications
listed in
. The ambient temperature (the enclosure air intake or room temperature) is especially
critical.
Table 46 Environmental operating specifications
Ambient temperature: +10 °C to +35 °C (+50 °F to +95 °F) with an average rate of change of 1 °C/hour
maximum and a step change of 3 °C or less. Maintaining the optimum ambient temperature within the
specified range ensures that the internal operating temperatures support the drive manufacturer’s MTBF
specifications.
Relative humidity: 40% to 60% (noncondensing) with a step change of 10% or less (noncondensing).
Air quality: Not to exceed a maximum of 500,000 particles, 0.5 micron or larger, per cubic foot of air.
Heat dissipation: 12,708 BTUs per hour.
When shipping, or placing this product in short term storage, HP recommends maintaining the
environmental conditions listed in
.
Table 47 Environmental shipping or short term storage specifications
Ambient temperature: –40 °C to +66 °C (–40 °F to +151 °F)
Relative humidity: 10% to 80% (noncondensing)
Altitude: below 15,240 m (50,000 ft)
Power specifications
defines the AC power specifications for the Enterprise Virtual Array PDUs, PDMs, drive enclosure
power supplies, and controller enclosure power supplies.
112