beautypg.com

Power specifications, Environmental specifications, 37 controller power supply ac power requirements – HP 3000 Enterprise Virtual Array User Manual

Page 110: 38 controller power supply output specifications, 39 ac input current and wattage

background image

Power specifications

Table 37

and

Table 38

define the controller power supply input power requirements and output power

specifications.

Table 37 Controller power supply AC power requirements

AC Input Voltage

Frequency

Minimum

Nominal

Maximum

Maximum

Minimum

180 VAC

202 VAC

220 VAC

47 Hz

50 Hz

208 VAC

57 Hz

60 Hz

208 VAC

240 VAC

254 VAC

Table 38 Controller power supply output specifications

Voltage Specification

Minimum

Nominal

Maximum

+3.3 VDC

Output Voltage Steady state current

Power

3.23 VDC

3.30 VDC

3.36 VDC 18 A

59.4W

+5.1 VDC

Output Voltage Steady state current

Power

4.80 VDC

5.00 VDC

5.25 VDC 5.0 A

25.5 W

Total Current Total Power

24 A 105.6 W

1.

+3.3 VDC steady state current requires a minimum 5.0-V load of 1 A.

2.

Total power includes 14.0 watts for the internal blower.

Table 39

defines the AC input current and wattage to the controller power supplies.

Table 39 AC input current and wattage

Nominal

Maximum

Input Voltage

Amps

Watts

Amps

Watts

60-Hz input

100 VAC

0.928

94

1.53

150

120 VAC

0.788

94

1.25

148

208 VAC

0.576

97

0.73

146

50–Hz Input

220 VAC

0.616

102

0.69

146

240 VAC

0.573

100

0.64

147

Environmental specifications

There are no controller environmental specifications. See

the section called “Environmental specifications”

for this information.

110

Regulatory notices and specifications