Set power baseline, Set power cap, Set asset info – HP ProLiant SL2500 Scalable System User Manual
Page 83
CLI commands 83
SET TIMEOUT 30
If you specify NONE, then no session timeouts are set. For example, enter:
SET TIMEOUT NONE
•
Description:
Sets the SSH and Telnet inactivity timeout.
Set power baseline
•
Command:
SET POWER BASELINE
•
Description:
Baseline or calibrate all servers that are connected to the HP APM. After you have established a
baseline for the configuration, it is saved into the EEPROM on the HP APM and the configuration
monitored for changes from the baseline configuration. Examples of changes to the configuration would
include the removal or installation of servers or chassis. If HP APM is reset, the baseline is re-read from
the EEPROM and compared to the discovered configuration after reset.
The baseline is computed for the entire configuration and is not applicable to zones. When a power
cap is set, the baseline data establishes the minimum and maximum power values that can be used for
the cap. If you set a cap with a defined zone specified, then only that baseline data that was established
for the enclosures and are within that zone are used to establish the minimum and maximum for the cap
to that zone.
Set power cap
•
Command:
SET POWER CAP
•
Description:
o
Establishes a power cap for all the eligible chassis that are connected to the HP APM.
The wattage value, if provided, represents the total wattage to be allocated among all the chassis
that are part of the baseline or partial baseline if a zone, if specified. This value is divided by the
total maximum wattage established by the baseline to come up with a percentage cap value. This
percentage is then multiplied against each chassis maximum wattage value to arrive at an
appropriate cap value for that individual chassis.
o
If you specify NONE instead of a cap wattage value, then HP APM removes all (or those in the
specified zone, if desired) of the power caps.
Set asset info
•
Command:
SET ASSETINFO [PDM1|PDM2] "
•
Description:
o
Enables HP APM to set an asset tag. Supported only on the HP 60A PDU.
o
The
into the PDU and can be retrieved with the SHOW ASSETINFO command.