Power capping 50

In the following figure, the HP APM port 2 is connected to the HP APM Distribution Module port 4. The
distribution module port is connected to the SL enclosure and server node 8.

Item

Description

1

HP APM

2

HP APM Distribution Module

3

SL series enclosure

4

Bay 4 of a 4U chassis SL6500 Scalable System enclosure with eight 1U half-width
nodes

Displaying the rack power status

Enter SHOW POWER, and then optionally the specific HP APM port, or both the HP APM and the HP APM

Distribution Module ports.
For example:

SHOW POWER (to show all power)
SHOW POWER 2 (to show the power for the HP APM port number)
SHOW POWER 2 4 (to show the power for the HP APM port number and the HP APM Distribution Module port

number
This command also displays:

Fan power per chassis in DC watts

Chassis total in DC watts

Chassis total in AC watts

Chassis cap in AC watts (if one is set)

The total of the averages is shown as well as the "average of averages" that was already there

The average max power is shown as well as the total of the max column