7 PROFIBUS DP data transfer

BU 0220 GB-0912

Subject to technical amendments

75

7.3.3

Writing a parameter

When transferring parameter orders, it must be taken into account that the slave does not immediately respond
to orders in the parameter channel of the master telegram, but a positive response can be delayed by one or
more communication cycles. The master must therefore repeat the required order until the corresponding slave
response is received. PPO type 1 or PPO type 2 must be selected (Section 7.2).

The parameter (P102) "run-up time" (PNU = 102

dec

/ 66

hex

) is to be set to the value 10sec in parameter set 3. (Only

the PKW channel is evaluated). (Only the PKW channel is evaluated.)

As the acceleration time has a frequency-internal resolution of 0.01sec, a parameter value of 10 / 0.01 = 1000
(3E8

hex

) must be transferred for 2 sec.

Procedure:

1) Specify order label ("Change parameter value (array word)"

→ AK = 7)

2) Select parameter (P 102

dec

+ 1000 = P 1102 = P 44E

hex

)

3) Select parameter set 3 (IND = 02)

4) Set parameter value (1000

dec

/ 3E8

hex

)

5) Check response telegram (positive for array word = 4)

The telegram is composed as follows in hexadecimal notation:

word

1

2

3

4

Byte

0

1

2

3

4

5

6

7

Designation

PKE

IND

PWE

PWE

Value

74

4E

02

00

00

00

03

E8

When the order has been fully implemented by the inverter, it responds with (hexadecimal):

word

1

2

3

4

Byte

3

4

5

6

7

8

9

10

Designation

PKE

IND

PWE

PWE

Value

44

4E

02

00

00

00

03

E8

ATTENTION

If parameter changes are made (i.e. requests via the PKW area by the control master), care
must be taken that the maximum number of permissible writing cycles to the frequency
inverter EEPROM (100,000 cycles) is not exceeded. I.e. continuous cyclical writing must be
prevented.

For certain applications it is sufficient if the values are only saved in the RAM memory of the
frequency inverter. The corresponding setting is made via parameter (P560) "Save in
EEPROM".