4.2.2.4 Profibus I/O Modules

This setting variant is exclusively reserved for the PROFIBUS DP module SK CU4-PBR or SK TU4-

PBR…)

which is connected to the system bus. This setting enables the DP master to directly access the digital I/Os of
the module. In this 1 byte module, the digital outputs must be set as "output byte" and the digital inputs as
"input byte".

The "Profibus module I/O" must always be set to Slot 1 in the DP slave.
If the additional I/Os are not used, an "empty module" must be set on Slot 1.

The bits are allocated to the inputs and outputs as follows:

NOTE

The digital inputs of the PROFIBUS DP modules (SK CU4-PBR and SK TU4-PBR-

…) cannot

be directly assigned with frequency inverter functionalities. These must be transferred via the
PROFIBUS and can be returned to the frequency inverter from the bus master via bits 8 and 9
of the control word by assignment of the required function in the BUS I/O In bits (P480 [-11] or
[-12]).

PLC I/Os

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

Inputs

n. c.

n. c.

n. c.

n. c.

DIN4

DIN3

DIN2

DIN1

Outputs

n. c.

n. c.

n. c.

n. c.

n. c.

n. c.

DO2

DO1