2 control clamp parameter (p400) – NORD Drivesystems BU0220 User Manual
Page 42
PROFIBUS DP
– Supplementary manualfor NORD Frequency Inverter SK 2xxE
42
Subject to technical amendments
BU 0220 GB-0912
5.1.2
Control clamp parameter (P400)
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P420
… [-01]
...
… [-04]
Digital inputs 1 to 4
0 ... 77
{ [-01] = 01 }
{ [-02] = 02 }
{ [-03] = 04 }
{ [-04] = 05 }
In the SK 200E, up to 4 freely programmable digital inputs are available. The only restriction is
with the versions SK 215E and SK 235E. Here, the fourth digital input is always the input for the
function "Safe Stop".
… [-01] = Digital input 1 (DIN1), Enable right as factory setting, control terminal 21
… [-02] = Digital input 2 (DIN2), Enable left as factory setting, control terminal 22
… [-03] = Digital input 3 (DIN3), fixed frequency 1 (P465 [-01]) as factory setting,
control terminal 23
… [-04] = Digital input 4 (DIN4), fixed frequency 2 (P465 [-02]) as factory setting,
(not with SK 215/235E "Safe Stop"), control terminal 24
Various functions can be programmed. For the complete list, please refer to the SK 200E
frequency inverter manual (BU0200).
NOTE:
The additional digital inputs of the field bus group are managed via parameter (P480).
Excerpt...
Value
Function
Description
Signal
00
No function
Input switched off.
---
…
14
1
Remote control
With bus system control, Low level switches the control to control
via control terminals.
High
…
1
Also effective for bus control (RS232, RS485, CANbus, CANopen, DeviceNet, Profibus, InterBus, AS-Interface)