5 Parameterisation
In order to enable communication via PROFIBUS DP, the frequency inverter and the PROFIBUS DP
technology Unit must be parameterised accordingly.
With the PROFIBUS DP protocol, the inverter parameters are mapped in the range 1000 to 1999, i.e. for
parameterisation via the bus in cyclic data traffic (PPO type 1 or 2) 1000 must be added to the parameter
numbers (e.g. (P508) - (P1508).
5.1 Parameterisation of frequency inverter SK 200E
The following list of parameters for the frequency inverter series SK 200E are directly relevant for the operation
of the frequency inverter via PROFIBUS DP. A complete list of parameters for the frequency inverter
(SK 200E) can be found in the relevant manual (BU0200).
5.1.1
Basic parameters (P100)
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P120
… [-01]
...
… [-04]
Option monitoring
S
0 ... 2
{ 1 }
Array levels:
Setting value for each array:
… [-01] = Extension 1 (BUS-TB)
… [-02] = Extension 2 (IO-TB)
… [-03] = Extension 3 (reserved)
… [-04] = Extension 4 (reserved)
0 = Monitoring OFF
1 = Auto, communication is only monitored if an
existing communication is interrupted. If a
module which was previously present is not
found after switching on the mains, this does
not result in an error
Monitoring only becomes active when an
extension starts communication with the FI.
2 = Monitoring active immediately; the FI starts
monitoring the corresponding module
immediately after it is switched on. If the
module is not detected on switch-on, the FI
remains in the status "not ready for switch-on"
for 5 seconds and then triggers an error
message.