3 example telegrams, 1 switch, On disabled → standby – NORD Drivesystems BU0220 User Manual
Page 72: 3 example telegrams 7.3.1
PROFIBUS DP
– Supplementary manualfor NORD Frequency Inverter SK 2xxE
72
Subject to technical amendments
BU 0220 GB-0912
7.3 Example telegrams
7.3.1
Switch-
on disabled → Standby
A frequency inverter is to be switched from the "Switch-on disabled" status (STW Bit 0
– 0), which is active
when the device is switched on, to the "Standby" status (STW Bit 0 = 1). The PPO type 1 (Section 7.2) is used,
however only the PZD channel is considered.
Procedure:
1) Check last status word (e.g. ZSW 0B 70)
2) Generate control word (STW 04 7E)
3) Check response telegram (ZSW 0B 31)
Procedure - Details
1) Check last status word (ZSW 0B 70)
word
5
6
Byte
8
9
10
11
Designation
ZSW
IW1
Value
0B
70
00
00
Bit
Value
Value
HEX
Meaning
15
0
0
Parameter set Bit 1 off
14
0
Parameter set Bit 0 off
13
0
Reserved
12
0
Rotation left is off
11
1
W
Rotation right is on
10
0
Reference value undershot
9
1
Bus controller
8
1
Setpoint = actual value
7
0
7
No warning
6
1
Starting disabled
5
1
No emergency stop
4
1
Voltage not disabled
3
0
0
No fault
2
0
Operation disabled
1
0
Not ready for operation
0
0
Not on standby
2) Generate control word (STW 04 7E)
The frequency inverter is set to Standby status with the following telegram.
word
5
6
Byte
8
9
10
11
Designation
STW
SW1
Value
04
7E
00
00