P514 can baud rate (system bus), P515, Can address (system bus) – NORD Drivesystems BU0220 User Manual
Page 45: P543, Actual bus value 1 … 3
BU 0220 GB-0912
Subject to technical amendments
45
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P514
CAN baud rate (system bus)
S
0 ... 7
{ 5 }**
Setting of the transfer rate (transfer speed) via the system bus interface. All bus participants
must have the same baud rate setting.
0 = 10kBaud
1 = 20kBaud
2 = 50kBaud
3 = 100kBaud
4 = 125kBaud
5 = 250kBaud**
6 = 500kBaud
7 = 1Mbaud *
*) Reliable operation cannot be guaranteed
**) for communication with the bus module, the parameter must be left at the factory setting
(250kBaud) otherwise no communication is possible.
P515
... [-01]
…
... [-03]
CAN address (system bus)
S
0 ... 255 dec
{ all 32 dec}
or { all 20 hex}
Setting of the system bus address.
… [-01] = Receive address for system bus
… [-02] = Broadcast – Receive address for system bus (slave)
… [-02] = Broadcast – Transmit address for system bus (master)
NOTE: If up to four SK 200E are to be linked via the system bus, the addresses must be set as follows
FI 1 = 32, FI 2 = 34, FI 3 = 36, FI 4 = 38.
The system bus addresses should be set via the DIP switches 1/2 (Section 2.2.3).
P543
… [-01]
...
… [-03]
Actual bus value 1 … 3
S
P
0 ... 24
{ [-01] = 01 }
{ [-02] = 04 }
{ [-03] = 09 }
The return value can be selected for bus actuation in this parameter.
NOTE:
For further details, please refer to the description for P418.
… [-01] = Actual bus value 1
… [-02] = Actual bus value 2 (only for PPO Type 2 or 4)
… [-03] = Actual bus value 3 (only for PPO Type 2 or 4)
Possible values which can be set:
0 = Off
1 = Actual frequency
2 = Actual speed
3 = Electricity
4 = Torque current (100% = P112)
5 = State of digital inputs and outputs
2
6 = ... 7 Reserved
8 = Setpoint frequency
9 = Error number
10 = ... 11 Reserved
12 = Bus Out bits 0...7
13 = ... 16 Reserved
17 = Value analog input 1 (BU0200)
18 = Value analog input 2 (BU0200)
19 = Setpoint frequency master value (P503)
20 = Setpoint frequency after master value
ramp
21 = Actual frequency without master value slip
22 = Speed from encoder
23 = Actual frequency with slip
24 = Master value, actual freq. with slip
2
The assignment of the dig. inputs for P543 = 5
Bit 0 = DigIn 1
(FI)
Bit 1 = DigIn 2
(FI)
Bit 2 = DigIn 3
(FI)
Bit 3 = DigIn 4
(FI)
Bit 4 = PTC input
[FI]
Bit 5 = Reserved
Bit 6 = DigOut 3
(DO1, 1.SK…IOE)
Bit 7 = DigOut 4
(DO2, 1.SK…IOE)
Bit 8 = DigIn 5
(DI1, 1.SK…IOE)
Bit 9 = DigIn 6
(DI2, 1.SK…IOE)
Bit 10 = DigIn 7
(DI3, 1.SK…IOE)
Bit 11 = DigIn 8
(DI4, 1.SK…IOE)
Bit 12 = DigOut 1
(FI)
Bit 13 = mech. brake
(FI)
Bit 14 = DigOut 2
(FI)
Bit 15 = Reserved