PROFIBUS DP

– Supplementary manualfor NORD Frequency Inverter SK 2xxE

46

Subject to technical amendments

BU 0220 GB-0912

Parameter

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter
set

P546

… [-01]

...

… [-03]

Function Bus setpoint 1 ... 3

S

P

0 ... 32

{ [-01] = 01 }

{ [-02] = 00 }

{ [-03] = 00 }

In this parameter, a function is allocated to the output setpoint during bus actuation.

NOTE:

For further details, please refer to the description for P400.

… [-01] = Bus setpoint value 1

… [-02] = Setpoint bus value 2 (only for PPO Type 2 or 4)

… [-03] = Setpoint bus value 3 (only for PPO Type 2 or 4)

Possible values which can be set:

0 = Off

1 = Setpoint frequency (16 bit)

2 = Frequency addition

3 = Frequency subtraction

4 = Minimum frequency

5 = Maximum frequency

6 = PI process controller actual value

7 = PI process controller setpoint

8 = Actual frequency PI

9 = Actual PI frequency limited

10 = Actual PI frequency monitored

11 = Limiting torque current

12 = Torque current switch-off limit

13 = Limiting current

14 = Current switch-off limit

15 = Ramp time

16 = Lead torque (P214) multiplication

17 = Multiplication

18 = Curve travel calculator

19 = Servo mode torque

20 = BusIO In Bits 0-7

21 = ...24 reserved for Posicon

31 = Digital output IOE

32 = Analog output IOE