6.2 Error messages
6.2.1
Table of possible error messages (caused by the bus) in the frequency inverter
The following error messages concern bus-related messages which are indicated on the frequency inverter. A
complete list of error messages for the frequency inverter (SK 200E) can be found in the relevant manual
(BU0200).
Display in the
SimpleBox
Fault
Text in the ParameterBox
Cause
Remedy
Group
Details in
P700[-01] /
P701
E010
10.0
Bus Timeout
(Telegram time-out /
Bus off 24V int. CANbus)
Data transfer is faulty. Check P513.
Check physical bus connections
Check Bus Master.
Check 24V supply of internal CAN/CANopen Bus.
Nodeguarding error (internal CANopen)
Bus Off error (internal CANbus)
10.2
External bus module
telegram timeout
(Timeout Profibus Watchdog)
Telegram transfer is faulty.
Check physical bus connections
PLC is in the "STOP" or "ERROR" state.
10.3
Timeout via (P151)
Telegram transfer is faulty.
Check watchdog time (P151)
Check physical bus connections
Check bus protocol program process.
PLC is in the "STOP" or "ERROR" state.
10.4
External bus module
initialisation failure
Profibus ASIC in the bus module cannot be accessed
10.8
External module
communication failure
Connection fault / error in the external module to the FI
10.9
Module not found
The module entered in parameter (P120) is not available.