2 Assembly and installation

BU 0220 GB-0912

Subject to technical amendments

27

2.2.3

Configuration

The configuration for all PROFIBUS DP module versions is identical. All necessary settings are made using
the hardware via a DIP switch element (3+8 part switching block).

Addressing

Note:

PROFIBUS DP - Address:

Setting only via DIP switch in binary code

Permissible address range:

3 … 125 → other addresses result in an error message

Address changes:

only become effective after switching the BUS module off and
on again

Termination resistor

The termination of the BUS system is made for the first and last participants by connecting the relevant
termination resistors (DIP switch).










E.g.: SK CU4-PBR

E.g.: SK 200E

PROFIBUS DP module (view of DIP switch)

SK 200E (internal view)

System bus

termination resistor

Field bus (PROFIBUS DP)
termination resistor

System bus
termination resistor

Customer unit SK CU4-PBR

Technology unit SK TU4-PBR

DIP switch 3 + 8 part

BUS termination