Control difference time, Alarm deadband, Internal electronics temperature lower limit – Badger Meter SRD/SRI Valve Positioners User Manual
Page 89: Internal electronics temperature upper limit

Control Difference Time
Default for this parameter is 60 seconds . This is a 4-byte real .
7
6
5
4
3
2
1
0
Control Diff
LoLo Alarm
HiHi Alarm
Low Alarm
High Alarm
NOT USED
More Status
Failsafe
Timeout
Alarm Deadband
This 4-byte real, expressed as percentage . As an example, if the Low alarm is set to 8%, and this parameter is set to 1%, the
default, then if the Low Alarm has occurred, the positioner needs to move back to 9% in order for the alarm to be cleared from
the secondary status .
Please note, the alarm is also recorded in the historical status . Thus it is possible to check if an alarm had occurred since the
last reset of historical status .
7
6
5
4
3
2
1
0
Control Diff
LoLo Alarm
HiHi Alarm
Low Alarm
High Alarm
NOT USED
More Status
Failsafe
Timeout
Internal Electronics Temperature Lower Limit
This is a 4-byte real field that allows the user to set a minimum value for the internal electronics temperature . If the internal
temperature of the positioner is outside the Lower Temperature Limit displayed in the alarms page, an alarm will be raised .
The diagnostic bit remains set as long as the condition is valid .
Default value is – 40° C (– 40° F) . Operating the positioner below this limit may cause damage to the instrument .
7
6
5
4
3
2
1
0
NOT USED
Trim Feedback
Trim Loop
Cycle Count
Travel Sum
Config invalid
Temp low
Temp high
Internal Electronics Temperature Upper Limit
This is a 4-byte real field that allows the user to set a maximum value for the internal electronics temperature . If the internal
temperature of the positioner is outside the Upper Temperature Limit displayed in the alarms page, an alarm will be raised .
The diagnostic bit remains set as long as the condition is valid .
Default value is 80° C (176° F) . Operating the positioner above this limit may damage the instrument and violate electrical
safety conditions .
7
6
5
4
3
2
1
0
NOT USED
Trim Feedback
Trim Loop
Cycle Count
Travel Sum
Config invalid
Temp low
Temp high
Pressure Sensor Page
Air Supply Pressure Lower Limit
This is a 4-byte real, expressed in the units defined in the Units page . It specifies the lower limit of the air supply pressure . If
the air supply pressure falls below this limit a status bit will be set .
Air Supply Scaling Low
This is a 4-byte real, expressed in the units defined in the Units page . It specifies the minimum value for scaling of the air
supply pressure, which is displayed in the Device Data Screen .
Air Supply Scaling High
This is a 4-byte real, expressed in the units defined in the Units page . It specifies the maximum value for scaling of the air
supply pressure, which is displayed in the Device Data Screen .
Output Pressure Scaling High
This is a 4-byte real, expressed in the units defined in the Units page . It specifies the maximum value for scaling of the output
pressure, which is displayed in the Device Data Screen .
Additional Status
Page 89
August 2014
POS-UM-00011-EN-02