Badger Meter SRD/SRI Valve Positioners User Manual
Page 67

Message
Status
Description /
Explanation
Recommended Action
Cycle Count Limit
Maintenance
Required
Cycle Count has
exceeded limit
configured .
Check valve performance and conduct maintenance if
necessary .
Input Loop Trim
Maintenance
Required
Input signal requires
calibration .
Perform Analog Setpoint Calibration procedure .
Feedback Trim
Maintenance
Required
Feedback unit requires
calibration .
Perform Angle Calibration procedure .
No Autostart done
—
No Autostart was done
or Autostart was run
and did not complete
successfully .
Ensure proper mounting of positioner and adequate supply
pressure . Refer to online Help for other potential causes . Rerun
Autostart Calibration procedure .
Position High Alarm Good
Position above High
Alarm Setpoint .
Monitor situation or correct cause .
Position Low Alarm
Good
Position below Low
Alarm Setpoint .
Monitor situation or correct cause .
Position High High
Alarm
Good
Position above High High
Alarm Setpoint .
Monitor situation or correct cause .
Position Low Low
Alarm
Good
Position below Low Low
Alarm Setpoint .
Monitor situation or correct cause .
Control Diff OOL
Maintenance
Required
Difference between
setpoint requested and
current position exceeds
allowed limit for a user
specified time .
Check to ensure that there is adequate supply pressure . Verify
tuning parameters . Check mechanics of actuator and valve .
Refer to troubleshooting section of SRD991 users manual .
Partial Stroke
Testing
—
The Partial Stroke
Testings allows to
evaluate if an Emergency
Shutdown Device (ESD)
will operate in case of a
safety shutdown .
The Partial Stroke Test can be found under the Configuration/
Partial Stroke . This is where the Test can be configured and
activated . The Testing Status shows the evaluation of the test .
Testing Status
Good
Not Done
A Partial Stroke Test has not been executed yet .
Good
Running
Test has been started and is in progress .
Local Operation
Restricted
Test is restricted . Either the valve is in control or the valve is not
fully open (100%) .
Good
OK
Test performed OK . The ESD capabilities have been tested and
showed that the valve is not stuck . The valve would move if a
safety system would close the valve .
Failure
Error
Test showed Error . The ESD capabilities cannot be guaranteed .
The valve is stuck and cannot move . The valve needs to be
inspected immediately!
Diagnostics
Page 67
August 2014
POS-UM-00011-EN-02