Restore Valve Specific Parameter
This function is required if a positioner is replaced without the option to
perform a new Autostart .
In this case, the function allows writing valve-specific parameters from
the replaced positioner into the new positioner . This is done by reading
the data file of one positioner mounted to a valve and writing these
values into a new positioner . This new positioner can then be adapted
to that valve without performing an Autostart .
The parameters for Lower End Position, Upper End Position, Motor
Parameter and ADC Gain have to be written into the unit . The values
of these parameters can be retrieved by means of the Parameter
List . However, if the parameters need to be edited, do so before
pressing Continue .
Due to mechanical tolerances in mounting, the adoption cannot be
optimal . Performing a new Autostart Calibration or Endpoint Calibration
is required as soon as possible .
NOTE:
N
This function is only allowed at workshop security level .
Language Download
See
Change Device Type
This function lets you change the type of the device . The following
device types are available:
• SRD991
• SRD960
• SRD970
• NAF-LinkIT
THIS FUNCTION IS ONLY FOR FACTORY USAGE. THE CHANGE OF THE
DEVICE TYPE ALSO CHANGES THE BEHAVIOR OF THE DEVICE TO A
CERTAIN DEGREE.
After you change the device type, you might have to change to a different DTM to connect to the device .
Reset Device / Reboot Device
The positioner will be rebooted during this procedure . The device behaves as if the power supply will be switched off and on .
This may cause a process upset . Press Continue to reboot the positioner, or Cancel to abort .
IF YOU REBOOT THE DEVICE, IT WILL OPEN AND CLOSE THE VALVE AND DISTURB THE PROCESS.