Status Overview
The Status Overview screen is a comprehensive display of all status of
the SRD991 .
It displays the result of the Primary, Secondary and Additional
status parts .
Before 02 .09 .2005
Message
Status
Description /
Explanation
Recommended Action
Temperature High
Out of Specification Temperature above
allowed limit .
Operation outside temperature limit (>80°C/176°F) may
damage positioner components and violate electrical safety
certification requirements . Stop operating positioner .
Temperature Low
Out of Specification Temperature below
allowed limit .
Operation outside temperature limit (<40°C/40°F) may damage
positioner components and violate electrical safety certification
requirements . Stop operating positioner .
Power Supply High
Out of Specification
Power Supply above
allowed limit .
4…20 mA / HART: Operation
above 22 mA
Fieldbus / FoxCom:
Operation above 12 mA
Operation outside power supply limit (see PSS for details) may
damage positioner components and violate electrical safety
certification requirements . Stop operating positioner . Ensure
that the maximum power allowed supply is supplied to the unit .
Power Supply Low
Out of Specification
Power Supply below
allowed limit .
4…20 mA / HART: Operation
below 3 .8 mA
Fieldbus / FoxCom:
Operation below 9 mA
Operation below power supply limit (see PSS for details) may
cause the positioner to go into failsafe . The communication
to the control system might be disturbed . Ensure that the
minimum power supply is supplied to the unit .
Air Supply Pressure
Alarm
Service /
Maintenance
Required
The Air Supply Pressure
falls below the
configured Lower Limit .
Check if the adequate supply pressure is applied .
Output Pressure
Alarm
Service /
Maintenance
Required
The positioner can not
regulate the Output
Pressure .
Check pneumatics . Check tubing to the actuator . Check for
leakages caused by the diaphragm .
Drag Pointer
for Maximum
Temperature
—
Shows the maximum
measured temperature
during operation .
Shows the exact value of the maximum temperature ever
measured to ensure that the High Temperature limits (>80° C,
176° F) are not reached .
Drag Pointer
for Minimum
Temperature
—
Shows the minimum
measured temperature
during operation .
Shows the exact value of the minimum temperature limit ever
measured to ensure that the Low Temperature limits (<40° C,
40° F) are not reached .
Invalid
Configuration
Maintenance
Required
Invalid configuration .
Correct configuration, perform Restore Factory Settings, rerun
Autostart procedure .
Travel Sum Limit
Maintenance
Required
Travel sum has exceeded
limit configured .
Check valve performance and conduct maintenance if
necessary .