Maintenance – history interval – Badger Meter SRD/SRI Valve Positioners User Manual
Page 53

Maintenance – History Interval
The History Intervals are used to configure the 4 different Historians for
the Position History and the Response History .
These Historians let you store and later upload the data from the
positioner memory for the specific time windows .
Later in operation, this lets you see what happened within the process,
showing the last 15 minutes (History 1), up to 24 hours (History 2), up to
30 days (History 3) and up to 60 months / 5 years (History 4) .
MPORTANT
I
Once the History Intervals are set, they should not be reconfigured during operation, because this will delete all stored data
of each Historian.
For details on how to reset the data, see Reset Valve Diagnosis .
History 1
Preset to 15 minutes . This History shows the last 15 minutes of the process for the Position History and the Response History .
The interval cannot be re-configured .
History 2
Preset to 24 hours . This History shows the last 1 to 24 hours of the process for the Position History and the Response History . The
interval can be configured between 1 to 24 hours .
History 3
Preset to 30 days . This History shows the last 1 to 30 days of the process for the Position History and the Response History . The
interval can be configured between 1 to 30 days .
History 4
Preset to 60 months . This History shows the last 1 to 60 months of the process for the Position History and the Response History .
The interval can be configured between 1 to 60 months .
Service Interval
The Service Reminder [in hours] is used in connection with the value for the Actual Time in Operation [in hours] . The Actual
Time in Operation provides the information how long the total operation time of this unit is . Once this value exceeds the value
configured under Service Reminder, a status bit is set, informing that the device needs to be serviced . In addition the Status of
Service Interval will switch from Good to Service . The device also shows the Time Since Last Service [in hours] .
Reminder After
Preset to 100 .000 hours . This Service Interval Reminder influences the Status of Service Interval, after this value exceeds the
Actual Time in Operation .
Years
Months
Days
Hours
0 .5
6
182 .5
4380
1
12
365
8760
2
24
730
17520
3
36
1095
26280
4
48
1460
35040
5
60
1825
43800
10
120
3650
87600
Configuration / Parameter
Page 53
August 2014
POS-UM-00011-EN-02