TECHNICAL DATA

74

H250

www.krohne.com

04/2011 - 4000269302 MA H250-R02 en

M10 binary output

Two binary outputs

Galvanically isolated

Operating mode

Switch output

NAMUR or open collector

Configurable as

Switch contact or

pulse output

open / closed or

max. 10 pulses / s

NAMUR switch output

Power supply

8 VDC

Signal current

> 3 mA switching value not

reached;

< 1 mA switching value

reached

Switch output, open collector

Power supply

8...30 VDC

P

max

500 mW

I

max

100 mA

M10 reset input

Binary input

Galvanically isolated

Operating mode

Reset counter

Configurable as

active Hi / active Lo

Voltage level

5...30 VDC

Current consumption

≤ 1 mA

Pulse length (active)

≥500 ms