ELECTRICAL CONNECTIONS

4

37

H250

www.krohne.com

04/2011 - 4000269302 MA H250-R02 en

4.4.3 Switching outputs B1 and B2

The switching outputs are electrically isolated from each other and from the current output.

Switching outputs B1 and B2 can be electrically connected in two ways:

• NAMUR switching output - Ri approx. 1 kOhm
• OC - (open collector) low-resistance switching output with PNP technology

Switching values

CAUTION!
The switching outputs can only be operating if the power supply is applied to terminals I+ and I-.

M10 - switching outputs

1 NAMUR terminal connection
2 Isolation switching amplifier
3 PNP technology terminal connection
4 Power supply
5 Load

NC contact

NO contact

NAMUR

OC

NAMUR

OC

Switching value reached

≤1 mA

≤1 mA

> 3mA

max. 100 mA

Switching value not reached

> 3mA

max. 100 mA

≤1 mA

≤1 mA

MA_H250_R02_en_269302_PRT.book Page 37 Tuesday, April 12, 2011 10:17 AM