4

ELECTRICAL CONNECTIONS

36

H250

www.krohne.com

04/2011 - 4000269302 MA H250-R02 en

HART

®

communication

When HART

®

communication is carried out with the M10, this will not in any way impair analogue

measured data transmission (4...20 mA).
Exception for multidrop operation. In multidrop operation, a maximum of 15 devices with HART

®

function can be operated in parallel, for which the current outputs are switched to inactive.

Load for HART

®

communication

The maximum load resistance is calculated as follows:

Configuration

The M10 electronic indicator can be configured via HART

®

communication. DD (Device

Descriptions) for AMS 6.x and PDM 5.2 as well as a DTM (Device Type Manager) are available for
configuration. They can be downloaded free of charge from our website.

The current flow rate can be transmitted using the integrated HART

®

communication. The flow

counter can be configured. Two limit values can be monitored. The limit values are assigned
either to flow values or to the counter.

INFORMATION!
For HART

®

communication a load of at least 230 ohm is required.

DANGER!
Use a twisted two-core cable to prevent electrical interference from impeding the DC output
signal.
In some cases a shielded cable may be necessary. The cable shield may only be earthed
(grounded) at one place (on the power supply unit).