FRAM WRITE
FAULT
Internal
communication error
Error
Check whether the display is plugged in
correctly and restart the device. If the error
occurs again: send the device back to the
manufacturer with an indication of the error.
ROM/FLASH
ERROR
Memory error
detected during self-
test.
Error
Restart the device. If the error occurs again:
send the device back to the manufacturer with
an indication of the error.
RESTART OF
DEVICE
A device restart has
taken place
Information
The device has been restarted using menu
item 1.5.2 since the last time the error
messages were reset.
MULTIDROP
MODE
The HART® multidrop
mode is activated.
The current output is
set to a fixed value of
4.5 mA.
Information
The HART®- multidrop mode is activated by
selecting a polling address not equal to 0
using menu item 3.9. A polling address of 0
reactivates the current output.
CRYSTAL OSC
FAULT
Internal error in
device
Error
The device must be sent back to the
manufacturer with an indication of the error.
REF VOLTAGE
FAULT
Internal error in
device
SENSOR A FAULT Internal error in
device
SENSOR B
FAULT
Internal error in
device
MEMORY
CORRUPTION
Internal memory
error, caused by a
hardware or software
problem
Error
Restart the device; if the error occurs again
the device must be sent back to the
manufacturer with an indication of the error.
AO FIXED
The current output is
set to a fixed value.
Information
The current output is fixed and does not
reflect the measured value. This is the case in
multidrop mode, with current output
test/calibration using the menu or HART®
AO SATURATED
Current output
saturated
Information
The current output is saturated at 20.4 or 22.0
mA (depending on whether the alarm current
is activated or deactivated in menu item 3.12),
and is no longer coupled with the measured
value.
Error message
Description
Category
Remedy