Device drivers for HART

®

tools, process control equipment (e.g. Siemens PDM or AMS)

PACTware

TM

and HART

®

DTMs are available on the internet site.

FRAM WRITE

FAULT

Internal

communication error

Error

Check whether the display is plugged in

correctly and restart the device. If the error

occurs again: send the device back to the

manufacturer with an indication of the error.

ROM/FLASH

ERROR

Memory error

detected during self-

test.

Error

Restart the device. If the error occurs again:

send the device back to the manufacturer with

an indication of the error.

RESTART OF

DEVICE

A device restart has

taken place

Information

The device has been restarted using menu

item 1.5.2 since the last time the error

messages were reset.

MULTIDROP

MODE

The HART® multidrop

mode is activated.

The current output is

set to a fixed value of

4.5 mA.

Information

The HART®- multidrop mode is activated by

selecting a polling address not equal to 0

using menu item 3.9. A polling address of 0

reactivates the current output.

CRYSTAL OSC

FAULT

Internal error in

device

Error

The device must be sent back to the

manufacturer with an indication of the error.

REF VOLTAGE

FAULT

Internal error in

device

SENSOR A FAULT Internal error in

device

SENSOR B

FAULT

Internal error in

device

MEMORY

CORRUPTION

Internal memory

error, caused by a

hardware or software

problem

Error

Restart the device; if the error occurs again

the device must be sent back to the

manufacturer with an indication of the error.

AO FIXED

The current output is

set to a fixed value.

Information

The current output is fixed and does not

reflect the measured value. This is the case in

multidrop mode, with current output

test/calibration using the menu or HART®

AO SATURATED

Current output

saturated

Information

The current output is saturated at 20.4 or 22.0

mA (depending on whether the alarm current

is activated or deactivated in menu item 3.12),

and is no longer coupled with the measured

value.

Error message

Description

Category

Remedy