ELECTRICAL CONNECTIONS

30

H250

www.krohne.com

04/2011 - 4000269302 MA H250-R02 en

4.3.3 Indicator M9 - Profibus PA (ESK3-PA)

Bus cable

Shielding and grounding

Shielding and grounding

Shielding and grounding

Shielding and grounding

The statements of the FISCO model only apply if the bus cable used meets the required
specifications. For specifications, see the chapter "Technical data" ESK3-PA.

In order to ensure optimum electromagnetic compatibility of systems it is important that the
system components, and in particular the bus cables, are shielded. These shields must have as
few gaps as possible.

Polarity reversal has no effect on the function. The cable shield should be connected with
minimum length to the functional ground FE.

Connection

Figure 4-5: ESK3-PA connection

1 Signal connection
2 Shielding and grounding