Technical data – KROHNE H250 M8-M9-M10 EN User Manual
Page 69
TECHNICAL DATA
8
69
H250
www.krohne.com
04/2011 - 4000269302 MA H250-R02 en
Indicator M8
Indicator M8
Indicator M8
Indicator M8
M8M limit switches
M8E current output
Terminal connection
2.5 mm
2
Limit switch
I7S2002-N
SC2-N0
SJ2-SN
SJ2-S1N
Type
2-wire NAMUR
2-wire NAMUR
1
2-wire NAMUR
1
Switch configuration
NC contact
NC contact
NO contact
Nominal voltage U
0
8 VDC
8 VDC
8 VDC
Pointer vane not read
≥ 3 mA
≥ 3 mA
≤1 mA
Pointer vane read
≤1 mA
≤1 mA
≥ 3 mA
1 safety oriented
Cable gland
M16 x 1.5
Cable diameter
8…10 mm
Terminal connection
4 mm
2
Measuring signal
4...20 mA = 0…100 % flow value in 2-wire technology
Power supply
14.8...30 VDC
Min. power supply for HART
®
20.5 VDC
Power supply influence
< 0.1%
Dependence on external resistance
< 0.1%
Temperature influence
< 10 µA / K
Max. external resistance / load
640 Ohm (30 VDC)
Min. load for HART
®
250 Ohm
M8E HART
®
configuration
Manufacturer name (code)
KROHNE Messtechnik (69)
Model name
M8E (230)
HART
®
protocol revision
5.1
Device revision
1
Physical layer
FSK
Device category
Transmitter
M8E process variable
M8E process variable flow rate
Values [%]
Signal output [mA]
Over range
+102,5 (±1%)
20,24...20,56
Device error identification
>106,25
≥21,00
Maximum
112,5
22
Multidrop operation
-
4,5