Operation – KROHNE H250 M8-M9-M10 EN User Manual

Page 54

background image

6

OPERATION

54

H250

www.krohne.com

04/2011 - 4000269302 MA H250-R02 en

3.14

LFC

LFC stands for Low Flow Cutoff.

With variable area flowmeters, the flow range from 0 to 10% is not

defined.

In order to ensure a stable zero point of the analogue output, the

analogue output can be set to a stable value of 4.00mA in a selectable

range from 0 to 20%.

3.14.1

CONTROL

INACTIVE

LFC is switched off

ACTIVE

LFC is switched on

3.14.2

LFC

ON_VALUE

1…19 %

Switch-on value 1:

The flow is greater than 20%.

The current output corresponds to this.

If the flow rate falls, then the current output follows it until the ON value.

If the flow value continues to fall, the current output is switched to

4.00 mA 3.

3.14.3

LFC

OFF_VALUE

2…20 %

Switch-off value 2:

The flow rate is 0. The current output is 4.00 mA 3.

If the flow rate rises, the current output remains at 4.00 mA 3 until the

OFF value, and is switched to the corresponding flow value if the flow

value rises further.

3.15

INP. CODE

YES

The input code is used to prevent authorised adjustment of the

measurement parameters.

The input code is not active by default.

If YES is selected, the last code entered must be typed in.

Factory code: → → → ^ ^ ^ ↑ ↑ ↑

If, after confirmation with YES, the button → is also pressed, then a new,

individual, nine-element code can be typed in.

The display shows the required key combination.

NO

3.16

BASIC

SETTING

YES

This menu item can be used to select the calibrated basic setting.

This can be helpful if operating data have been changed a number of

times.

This menu item cannot be used to reset the calibration.

NO

Level Designation

Selection /
Input

Explanation