ELECTRICAL CONNECTIONS

4

29

H250

www.krohne.com

04/2011 - 4000269302 MA H250-R02 en

Load for HART

®

communication

The maximum load resistance is calculated as follows:

Configuration

The ESK can be configured via HART

®

communication. DD (Device Descriptions) for AMS 6.x and

PDM 5.2 as well as a DTM (Device Type Manager) are available for configuration. They can be
downloaded free of charge from our website.

The current flow rate can be transmitted using the integrated HART

®

communication. A flow

counter can be configured. Two limit values can be monitored. The limit values are assigned
either to flow values or to the counter overflow.

Self monitoring - Diagnostics

During both start-up and operation, a wide variety of diagnostic functions are performed
cyclically in the ESK2A, in order to guarantee function reliability. When an error is detected, a
failure signal (high) is activated (current > 21 mA) via the analogue output. In addition, more
detailed information can be requested via HART

®

(CMD#48). The failure signal is not activated

for information and warnings.

Diagnostic functions (Monitoring):

• Plausibility of FRAM data
• Plausibility of ROM data
• Working range of internal reference voltages
• Signal detection of the measuring range of the internal sensors
• Temperature compensation of the internal sensors
• Calibration corresponding the application
• Plausibility of counting value
• Plausibility of physical unit, system and selected unit

INFORMATION!
For HART

®

communication a load of at least 230 ohm is required.

DANGER!
Use a twisted two-core cable to prevent electrical interference from impeding the DC output
signal.
In some cases a shielded cable may be necessary. The cable shield may only be earthed
(grounded) at one place (on the power supply unit).

MA_H250_R02_en_269302_PRT.book Page 29 Tuesday, April 12, 2011 10:17 AM