Technical data – KROHNE H250 M8-M9-M10 EN User Manual
Page 70
8
TECHNICAL DATA
70
H250
www.krohne.com
04/2011 - 4000269302 MA H250-R02 en
Indicator M9
Indicator M9
Indicator M9
Indicator M9
M9 cable glands
M9 limit switches
M9 current output ESK2A
Cable gland
Material
Cable diameter
M 16x1.5 Standard
PA
3...7 mm
0.118...0.276"
M20 x 1.5
PA
8...13 mm
0.315...0.512"
M 16x1.5
Nickel-plated brass
5...9 mm
0.197...0.355"
M20 x 1.5
Nickel-plated brass
10...14 mm
0.394...0.552"
Terminal connection
2.5 mm
2
Limit switch
I7S23,5-N
SC3,5-N0
SJ3,5-SN
1
SJ3,5-S1N
1
SB3,5-E2
NAMUR
yes
yes
yes
no
Connection type
2-wire
2-wire
2-wire
3-wire
Switching element
function
NC contact
NC contact
NO contact
PNP NO contact
Nominal voltage U
0
8 VDC
8 VDC
8 VDC
10...30 VDC
Pointer vane not detected
≥ 3 mA
≥ 3 mA
≤ 1 mA
≤ 0.3 VDC
Pointer vane detected
≤ 1 mA
≤ 1 mA
≥ 3 mA
U
B
- 3 VDC
Continuous current
-
-
-
max. 100 mA
No load current I
0
-
-
-
≤ 15 mA
1 safety oriented
Terminal connection
2.5 mm
2
Power supply
12...30 VDC
Min. power supply for HART
®
18 VDC
Measuring signal
4.00...20.00 mA = 0...100% flow value in 2-wire technology
Power supply influence
<0.1%
Dependence on external resistance
<0.1%
Temperature influence < 10µA / K
Max. external resistance / load
800 Ohm (30 VDC)
Min. load for HART
®
250 Ohm
Software firmware version
02.15
Ident No.
4000054602
ESK2A HART
®
configuration
Manufacturer name (code)
KROHNE Messtechnik (69 = 45h)
Model name
ESK2A (226 = E2h)
HART
®
protocol revision
5.9
Device revision
1
Physical layer
FSK
Device category
Transmitter without galvanic isolation
MA_H250_R02_en_269302_PRT.book Page 70 Tuesday, April 12, 2011 10:17 AM