ELECTRICAL CONNECTIONS

26

H250

www.krohne.com

04/2011 - 4000269302 MA H250-R02 en

If the pointer vane enters the slot, an alarm is triggered. If the pointer vane lies outside the slot
sensor, a wire break also causes the alarm to be triggered.

The 3-wire limit switch does not have any wire break detection.

Current consumption in the position shown:

Switch contact definition

1 MIN contact
2 MAX contact
3 Pointer vane with switching vane

Definition MinMin - MaxMax

1 MIN 2 contact or MAX 1 contact
2 MIN 1 contact or MAX 2 contact

Contact

Type

Current

MIN 1

NAMUR

≤ 1 mA

MIN 2

NAMUR

≤ 1 mA

MAX 1

NAMUR

≥ 3 mA

MAX 2

NAMUR

≥ 3 mA