Default (4/2) event codes – Edwards Signaling FireShield 10 Zone User Manual
Page 62
Default event codes
E.2
FireShield Technical Reference Manual
Default (4/2) event codes
Code
Description
1
Fire alarm activation events
2
Waterflow alarm activation events
3
Supervisory signal activation events
4
Not used
5
Monitor signal activation events
6
NAC trouble activation events
65
Aux power trouble activation
66
Ground fault activation
67
DACT delivery trouble
68
DACT line 1fail
69
AC loss
6A
Transformer 2 trouble
6B
Charger trouble
6C
Battery missing/Battery bad
6D
FSRSI, FSRZI, FSRRM trouble
6E
DACT line 2 fail
6F
DACT abnormal test
7
IDC trouble activation
8
IDC disabled (not configurable)
9
IDC enabled (not configurable)
A
NAC disabled (not configurable)
A5
FSRRM outputs disabled (not configurable)
AA
Internal communication trouble
AB
Panel reset
AC
Signal silence activated
AD
Drill activated
AE
DACT disabled
AF
Walk test activated
B
NAC enabled (not configurable)
B5
FSRRM outputs enabled (not configurable)
BB
Panel reset restore (not configurable)
BC
Signal silence ended (not configurable)
BD
Drill ended (not configurable)
BE
DACT enabled (not configurable)
BF
Walk test ended (not configurable)
C1
Program mode entry
C2
Program mode exit (not configurable)
CA
Panel silence activated
D
NAC trouble restoration
D5
Aux power trouble restoration
D6
Ground fault restoration
D7
DACT delivery trouble restore
D8
DACT line 1 restoration
D9
AC loss restoration
DA
Transformer 2 restoration
DB
Charger trouble restoration
DC
Battery missing/Battery bad restore
DD
FSRSI, FSRZI, FSRRM restoration
DE
DACT line 2 restoration
DF
DACT normal test
E
Fire alarm restoration
E
Waterflow alarm restoration
Code
Description
E
Supervisory restoration
E
Monitor restoration
F
IDC trouble restoration
Note: N is the circuit number.