Programming templates
FireShield Technical Reference Manual
B.3
System event reporting setup
Event
Where to report the event
4/2 event code
Panel test
None
CS 1
CS 2
CS 1 & 2
DF
Panel abnormal test
None
CS 1
CS 2
CS 1 & 2
6F
Walk test
None
CS 1
CS 2
CS 1 & 2
AF
Drill
None
CS 1
CS 2
CS 1 & 2
AD
Reset
None
CS 1
CS 2
CS 1 & 2
AB
Program mode
None
CS 1
CS 2
CS 1 & 2
C1
DACT Disabled
None
CS 1
CS 2
CS 1 & 2
AE
Panel silence
None
CS 1
CS 2
CS 1 & 2
CA
Signal silence
None
CS 1
CS 2
CS 1 & 2
AC
Ground fault
None
CS 1
CS 2
CS 1 & 2
66
Low battery
None
CS 1
CS 2
CS 1 & 2
6C
Missing battery
None
CS 1
CS 2
CS 1 & 2
6C
Internal comm trouble
None
CS 1
CS 2
CS 1 & 2
AA
AC fail
None
CS 1
CS 2
CS 1 & 2
69
Charger trouble
None
CS 1
CS 2
CS 1 & 2
6B
Transformer 2 trouble
None
CS 1
CS 2
CS 1 & 2
6A
Aux power trouble
None
CS 1
CS 2
CS 1 & 2
65
Peripheral trouble
None
CS 1
CS 2
CS 1 & 2
6D
DACT line 1 trouble
None
CS 1
CS 2
CS 1 & 2
68
DACT line 2 trouble
None
CS 1
CS 2
CS 1 & 2
6E
DACT delivery trouble
None
CS 1
CS 2
CS 1 & 2
67
System trouble restoral (4/2 code)
(0 – F) D
Zone settings - IDC 1
Note: For IDCs, program only those events that apply to the IDC zone type you specified on the “Panel programming worksheet.”
Event
Where to report the event
4/2 event code
Alarm activation
None
CS 1
CS 2
CS 1 & 2
11
Waterflow activation
None
CS 1
CS 2
CS 1 & 2
21
Trouble activation
None
CS 1
CS 2
CS 1 & 2
71
Supervisory activation
None
CS 1
CS 2
CS 1 & 2
31
Monitor activation
None
CS 1
CS 2
CS 1 & 2
51
Zone settings - IDC 2
Event
Where to report the event
4/2 event code
Alarm activation
None
CS 1
CS 2
CS 1 & 2
12
Waterflow activation
None
CS 1
CS 2
CS 1 & 2
22
Trouble activation
None
CS 1
CS 2
CS 1 & 2
72
Supervisory activation
None
CS 1
CS 2
CS 1 & 2
32
Monitor activation
None
CS 1
CS 2
CS 1 & 2
52
Zone settings - IDC 3
Event
Where to report the event
4/2 event code
Alarm activation
None
CS 1
CS 2
CS 1 & 2
13
Waterflow activation
None
CS 1
CS 2
CS 1 & 2
23
Trouble activation
None
CS 1
CS 2
CS 1 & 2
73
Supervisory activation
None
CS 1
CS 2
CS 1 & 2
33
Monitor activation
None
CS 1
CS 2
CS 1 & 2
53
Note: Default settings are shown in boldface type.