Panel specifications, Appendix d – Edwards Signaling FireShield 10 Zone User Manual
Page 59
FireShield Technical Reference Manual
D.1
Appendix D
Panel specifications
FS302 three-zone
panel
FS502 five-zone panel
FS1004 ten-zone panel
Class B
3
5
3
1
10
8
6
4
2
0
Initiating device
circuits (IDCs)
Class A
0
0
1
2
0
1
2
3
4
5
Class B
2
2
0
4
2
0
Notification appliance
circuits (NACs)
Class A
0
0
1
0
1
2
Power supply
2.0 amps total
3.0 amps total
3.0 amps (expandable to 5.5 amps)
NAC voltage rating
24 Vfwr
Maximum NAC current
1.5 amps each
1.5 amps total
1.5 amps each
2.5 amps total
1.5 amps each - 2.5 amps total for
NAC1 + NAC2 or NAC3 + NAC4
5.0 amps with optional
expander transformer
120 Vac 60 Hz
0.8 amps
0.8 amps
1.6 amps - incl. optional exp. transformer
AC input
230 Vac 50/60 Hz
0.4 amps
0.4 amps
0.8 - incl. optional exp. transformer
Base panel current draw (standby)
110 mA
120 mA
145 mA
Base panel current draw (alarm)
145 mA
170 mA
250 mA
Battery placement
Up to two 7 Ah batteries will fit in the panel.
Note: If batteries greater than 7 Ah are required,
you must use the BC-2 battery cabinet. Refer to
installation sheet P/N 3100027.
Up to two 18 Ah batteries will fit in the
panel.
Maximum auxiliary current
0.5 amps (may be programmed as resetable)
Auxiliary output
19 to 25.7 Vdc
IDC max. detector standby current
1.5 mA (See FireShield UL and ULC Compatibility List (P/N 3100468)
for maximum quantity of detectors per circuit.)
IDC circuit
Maximum loop resistance: 13
Ω
Maximum loop capacitance: 0.03
µ
F
IDC operating voltage
16.3 to 25.7 Vdc
Compatibility ID
100
Alarm contact
Form A N.O. 30 Vdc @ 1 A (resistive load)
Trouble contact
Form C 30 Vdc @ 1 A (resistive load)
Supervisory contact
Form A N.O. 30 Vdc @ 1 A (resistive load)
Environmental
Temperature: 0 to 49 °C (32 to 120 °F)
Humidity: 5 to 93% RH, noncondensing
Terminal rating
All terminals rated for 12 to18 AWG (0.75 to 2.5 sq mm)
Serial communications
Asynchronous communications maximum resistance: 13
Ω
Maximum capacitance: 0.03
µ
F
Batteries
Batteries must be sealed lead acid type only. Maximum charging capacity = 18 Ah.