Installing the remote zone indicator – Edwards Signaling FireShield 10 Zone User Manual
Page 13
Installation
FireShield Technical Reference Manual
2.3
Compatible electrical box
Installing the FSRSI in an electrical box
Wiring diagram
Group
J2
24V IN
- +
C IN
+ -
C OUT
+ -
24V OUT
- +
24 V in +
24 V in -
Communication in -
Communication in +
Communication out +
Communication out -
From control panel
or previous device
To next device
24 V out +
24 V out -
Notes
1. All wiring is supervised and power limited.
2. 24 V out (aux power) must be programmed as non-
resettable.
Installing the Remote Zone Indicator
The Remote Zone Indicator (FSRZI-A) is a supervised remote
annunciator that provides remote LED indication of IDCs in
alarm state. The FSRZI-A indicates conditions for five IDCs.
The IDC groups are set by jumpers to indicate zones 1–5 or
zones 6–10. Paper inserts are provided for labeling the LEDs.
Note:
You must run the Find Annunciators program option
after adding or removing a remote annunciator. The remote
annunciators will not operate properly until the panel detects
them. For more information see Chapter 3 “Programming.”
Specifications
Max. per system
FS302 (three-zone): 2
FS502 (five-zone): 2
FS1004 (ten-zone): 4
Voltage range
Minimum: 21 Vdc
Maximum: 25 Vdc
Current requirements
Standby: 8 mA
Alarm: 35 mA
Max. circuit capacitance: 0.03
µ
F
Max. circuit resistance: 13 ohms
Wire size
Minimum: 18 AWG (0.75 sq mm)
Maximum: 12 AWG (2.5 sq mm)
Compatible electric box: ANSI/NEMA OS1-1996 1-3 gang
electrical box
Operating environment
Temperature: 32 to 120 °F (0 to 49 °C)
Humidity: 93% RH, noncondensing