Edwards Signaling FireShield 10 Zone User Manual
Page 56
Jumper settings and wiring diagrams
C.4
FireShield Technical Reference Manual
Keep power-limited wiring in the shaded
area and nonpower-limited wiring in the
unshaded area at all times.
NOTES
1
All wiring is power-limited except for AC power and battery wiring. All wiring
is supervised unless noted otherwise.
[2]
Class A wiring not supported
[3]
Listed EOLRs must be installed as shown for proper supervision
[4]
For UL installations use EOLR P/N EOL3.6-1.1 which includes one 1.1 k
(P/N EOL1.1) and one 3.6 k (P/N EOL3.6) resistor. For ULC installations
use EOL-P1 and select the 1.1 k and 3.6 k resistors.
Ω
Ω
Ω
Ω
[5]
Marking indicates output signal polarity when the circuit is active. Polarity
reverses when the circuit is not active. Wire notification appliances
accordingly. Notification appliance polarity shown in active state.
1.1 k
Ω
3.6 k
Ω
IDC1–
IDC1+
SS
SS
WF
WF
REMOTE MODULE AND
REMOTE RELAY WIRING [6]
POWER
ALARM
SUP
TBL
GND FLT
SILENCE
LMPTST
C–
C+
24VDC+
24VDC–
REMOTE
RELAY
MODULE
(RRM)
WATERFLOW / SUPERVISORY COMBINATION CIRCUIT [4] [8]
[6]
Requires continuous 24 Vdc from the AUX Power
terminals or a power-limited UL/ULC listed compatible
fire signaling power supply
[7]
IDC circuits do not support alarm verification using four-
wire smokes. Requires resettable 24 Vdc from AUX
Power terminals.
[8]
Combination circuits consist of waterflow switches (WF)
and their associated valve tampers (SS).
[10] Relay circuits can only be connected to power-limited
sources
[11] Installation limits under jurisdiction of local authority
[12] Refer to the
(P/N 3100353) for the topic "Installing the FSDACT."
[9]
Automatic and manually activated alarm initiating
devices can be installed on the same IDC circuit
regardless of circuit type except for combination circuits
(option 6, setting 5 and 6)
FireShield Technical Reference Manual
TYPICAL FOUR-WIRE
SMOKE DETECTOR CIRCUIT [2] [3] [7]
4.7 k
Ω
UL/ULC LISTED
EOL RELAY
(shown energized)
IDC1+
24VDC–
24VDC+
IDC1–