beautypg.com

Edwards Signaling FireShield 10 Zone User Manual

Page 36

background image

Programming

3.14

FireShield Technical Reference Manual

28. Enter the call back phone number

Description: Specifies the phone number that is used for call
back.

Format: Up to 20 digits

Default: Blank

To enter the call back phone number:

1. Press Reset until the first digit of the phone number is

displayed.

2. Press Panel Silence to save and advance to the next digit.

The trouble buzzer sounds a long beep as confirmation.

3. Press Reset until the next digit is displayed.

4. Press Panel Silence to save and advance to the next digit.

5. Repeat steps 3 and 4 until all digits are entered.

Note:

If less than 20 digits are entered, press Panel

Silence again or Remote Disconnect to advance to the
next program option.

6. When you press Reset at the last digit (20th digit), the

system automatically advances you to the next program
option.

Event notification programming

Event notification programming determines where events are
sent. Events can be sent to the primary, secondary, or both
central monitoring stations (CMS), or you can choose not to
send the event at all.

To program event notification, follow these general steps:

1. Select CMS locations for event reporting
2. Enter the system trouble restore code

Note:

If you are only using one central monitoring station and

are using the default settings, no further programming is
required. You can exit from programming by removing the
program jumper.

The first event notification programming option after
completing “Select the restore option” is “Panel Tst Rcvr.”
Twenty-one event receiver locations must be programmed
using steps described below, under “Select CMS locations for
event reporting.”
CS Tst Rcvr
CS AB Tst Rcvr
Walk Tst Rcvr
Drill Rcvr
Reset Rcvr
Program Mode Rcvr
DACT Disab Rcvr
Panel Sil Rcvr
Signal Sil Rcvr
Grd Fault Rcvr

Low Batt Rcvr
Mis Batt Rcvr
Int Comm Tr Rcvr
AC Fail Rcvr
Charger Tr Rcvr
Xfrmr 2 Tr Rcvr
Aux Pwr Tr Rcvr
Periph Trb Rcvr
Line 1 Trb Rcvr
Line 2 Trb Rcvr
Delivery Tr Rcvr

After programming the receiver locations, continue with the
steps described under “Enter the system trouble restore code.”

1. Select CMS locations for event reporting

Description: Specifies which CMS receives each event.

Settings: None
CS

1

CS

2

CS 1 and 2

Default: CS 1

To select the CMS locations for event reporting:

1. Press Reset to select the desired CMS location.

2. Press Panel Silence to save and advance to the next

program option.

The trouble buzzer sounds a long beep as confirmation.

3. Repeat steps 1 and 2 to set the CMS location for each

option.

4. When you reach the last option, proceed to "Enter the

system trouble restore code" below.

2. Enter the system trouble restore code

Description: Sets the code that is transmitted to the CMS with
trouble restoral events.

Format: 1 digit (0 – 9 and A – F)

Default: See Appendix E “Default event codes.” This can be
changed if needed.

To enter the system trouble restore code:

1. Press Reset to increment the restore code if it needs to be

changed.

2. Press Panel Silence to save and advance to the next

program option.

The trouble buzzer sounds a long beep as confirmation.

This manual is related to the following products: